Disabled Refuge Alarm Testing & Servicing

A comprehensive check and test sequence should be carried out by a competent person every 6 months, in accordance with British Standards for Fire Detection and Fire Alarm Systems for Building BS5839 part 9.

Angus Stone
A chartered electronics engineer with over 40 years experience in Emergency Lighting and Fire Detection and Alarm systems.

Angus has been involved in developing and writing British and International Fire & Safety standards since the mid-1980s. The list of standards that he has participated in is impressive and includes BS5839-1, BS8629, EN54-18 and ISO7240-2.  Angus utilises his extensive experience to provide an authoritative perspective on the key issues that affect the Fire & Security Industry today.

Angus has been involved in developing and writing British and International Fire & Safety standards since the mid-1980s. The list of standards that he has participated in is impressive and includes BS5839-1, BS8629, EN54-18 and ISO7240-2.  Angus utilises his extensive experience to provide an authoritative perspective on the key issues that affect the Fire & Security Industry today.

Disabled Refuge Alarm testing, serving and maintenance should be carried out in accordance with the manufacturer’s instructions and current British Standard 5839 Part 9.

The following tests/inspections should be carried out.

Daily Visual Checks of Disabled Refuge Alarm

In premises in which the location of the master station is such that the audible fault warning signal could go unnoticed for longer than 24 hours, a special check should be carried out each day to confirm that either the equipment indicates normal operation or that any fault indication is receiving the necessary attention.

Weekly Checks of Disabled Refuge Alarm

Every week, an outstation should be operated, it should be confirmed that the call is correctly received at the master station and that a short test conversation is clear and intelligible at both the master station and outstation.

A different outstation should be used at the time of every weekly test so that all outstations in the building are tested in rotation.

The devices tested and results should be recorded in the Log Book following each test.

Monthly Checks of Disabled Refuge Alarm

If an automatically started emergency generator is used as part of the secondary power supply to the Disabled Refuge Alarm System, it should be started up once each month by simulation of failure of the primary power supply and operated on-load for at least one hour. The test should be carried out in accordance with the instructions of the generator manufacturer, including instructions on the load that should be operated. At the end of the test, the fuel tanks should be left filled, and oil and coolant levels should be checked and topped up as necessary.

If a vented battery is used as a secondary power supply, a visual inspection of the battery and its connections should be made to ensure that it is in good condition. Action should be taken to rectify any defect, including low electrolyte level.

Note: Care needs to be taken to ensure that any person undertaking this task is competent to do so safely.

Periodic Planned Maintenance of Disabled Refuge Alarm

A comprehensive check and test sequence should be carried out by a competent person every 6 months, in accordance with British Standards for Fire Detection and Fire Alarm Systems for Building BS5839 part 9. Following each Planned Maintenance, the results should be recorded by the engineer in the Fire Log Book.

Got a question about Disabled Refuge Alarms? Need Fire Safety Compliance advice? Get in touch today.

For over 45 years, Fixfire® has been providing quality products, systems, and services for Life & Property Protection. Whatever your requirement, please call our Compliance Team for expert advice and a refreshingly different approach.

Freephone 08000891999

You have a legal duty of care to dispose of waste legitimately and safely via a licensed waste carrier. Failure to do so can result in prosecution, even if you have outsourced the disposal to a third party.

The Fixfire® Extinguisher Recycling Process is your reassurance that any Fire Extinguishers we remove from your premises have been disposed of in a safe and legal manner. 97% of each processed Fire Extinguisher is recycled.

Our contracted Extinguisher Recycling Unit (ERU) is a dedicated facility offering a service for the safe processing and recycling/disposal of fire extinguishers. The facility operates closely with the local Water Authority and the Environment Agency to develop safe, efficient and environmentally friendly processes, ensuring that ISO14001 certification is upheld.

Got a question about Fire Extinguisher Disposal?  Need Fire Safety Compliance advice? Get in touch today!

For over 45 years, Fixfire® has been providing quality products, systems and services for Life & Property Protection. Whatever your requirement, please call our Compliance Team for expert advice and a refreshingly different approach.

Freephone 08000 891999

Our contracted Extinguisher Recycling Unit (ERU) is a dedicated facility offering a service for the safe processing and recycling/disposal of fire extinguishers. The facility operates closely with the local Water Authority and the Environment Agency to develop safe, efficient and environmentally friendly processes, ensuring that ISO14001 certification is upheld.

Got a question about Fire Extinguisher Disposal?  Need Fire Safety Compliance advice? Get in touch today!

For over 45 years, Fixfire® has been providing quality products, systems and services for Life & Property Protection. Whatever your requirement, please call our Compliance Team for expert advice and a refreshingly different approach.

Freephone 08000 891999

False Fire Alarms remain a huge concern within the education sector- interrupting already carefully scheduled, planned and well-prepared lessons or even causing major disruption and distress to exams.  

Clearly, these false alarms cause significant inconvenience and disruption to students, staff, and visitors. They compromise everyone’s safety in the school and present a significant risk to the local community since the Fire Brigade will prioritise the school over other emergency callouts.

Solutions you should consider:

Anti-tamper products

The first and most straightforward way is to use anti-tamper products.

Fixfire® supplies a wide range of solutions designed to protect Fire Alarm Devices from inadvertent damage or deliberate misuse/vandalism.

Products include:

  • Local plastic cover flaps which attach directly to manual call points.
  • The stopper consists of a clear, tamperproof, tough polycarbonate cover, frame and spacer that retrofits over a break glass call point. When lifted to operate the break glass unit, its optional battery powered integral sounder emits a piercing 96dB (at 1m). Immediate attention is drawn to the area and a prankster will either run or be caught!
  • A range of steel web stoppers designed to protect fire detectors and warning devices. They are constructed from heavy-duty galvanised steel rod which is plastic-coated for durability and external use.
  • A range of polycarbonate enclosures are available for the protection of devices such as fire alarm control panels and associated control equipment. The enclosures combine tough rugged construction with stylish design and offer excellent protection with a key lock for authorised access.

We also provide anti-tamper devices for fire extinguishers and associated products.

KeyCall® Call Point

KeyCall® is a patented anti-ligature Fire Alarm and Access Control call point. It is designed to use the same key as the doors, providing simple operation for staff whilst eliminating nuisance activations by service-users.

KeyCall® has been developed by Fixfire® specifically for approved applications where standard versions would be vulnerable to abuse.

It is one of the best solutions for SEN schools and it is also compatible with a wide range of Conventional and Addressable Fire Alarm Systems.

Conduct Fire Safety Training

Most fire safety courses offer a mix of classroom-based learning and practical training experience, educating attendees on how to respond in the event of an emergency.

 In order to fulfil your obligations under current Fire Safety Law, it is essential that you have a documented regime of Fire Safety tests and checks and personnel who are suitably trained to respond correctly in the event of an emergency.

All Fire Safety Training is provided by experienced, time-served and qualified persons from a Fire Safety background.

Video surveillance

Even if the cameras don't identify the culprit, they can identify who was in the area at the time of the false alarm activation. Fixfire® specialises in integration and will bring together your Fire, Access and Security systems providing enhanced functionality.

Fixfire® provides leading-edge integration with ancillary systems and equipment. Our mission is to deliver reliable, well-engineered installations that provide you with peace of mind 24/7.

Place fire detectors in the correct locations

Smoke detectors that are placed too close to kitchens, cooking appliances, locker rooms or bathrooms will most likely be accidentally activated by the smoke or steam emitted by these sources. Detectors might need to be relocated.

Smoke detectors are more sensitive and are installed in any environment where smoke or steam would not normally be present. Heat detectors are installed in areas such as kitchens where smoke detectors would constantly false alarm during routine cooking. Multi-sensors combine smoke and heat in one detector and offer immunity to false alarms in certain applications.

Use the right detector

New detectors have improved technology and can measure a range of conditions to potentially be more effective at detecting a fire condition.

Flush Fire Detectors ensure protection is not compromised in any areas where conventional ‘un-pluggable’ detection could be subject to abuse. It is widely used in SEN Schools.

Maintain your Fire System

Make sure the alarm system is properly and regularly maintained.

Fixfire® is BAFE accredited for the Design, Installation, Maintenance and Servicing of Fire Alarm Systems.

All works are carried out by our employed, uniformed and trained Fire Alarm engineers.
Following each visit, a Certificate of Inspection is issued.

Got a question about False Fire Alarms? Need Fire Safety Compliance advice?  Get in touch today!

For over 45 years, Fixfire® has been providing quality products, systems and services for Life & Property Protection. Whatever your requirement, please call our Compliance Team for expert advice and a refreshingly different approach.

Freephone 08000 891999

Disabled Refuge Alarm Systems
Disabled Refuge Alarm Systems
Download Your Guide
Disabled Refuge Alarm Testing - Everything You Need To Know
Related Links
Free site assessments, personal service & helpful advice. Contact us today!
Contact us today
08000 891 999
GET IN TOUCH